What is Fabric Light Box or Textile Light Box?

What is Fabric Light Box or Textile Light Box?

Fabric Light Box or Textile Light Box

A standardized fabric light box or textile light box is used for visual assessments to maintain consistency in light source, viewing area and presentation of sample.All shade assessment and colour matching must be carried out in a purpose built colour matching cabinet named Fabric light box or textile light box which can be purchased from several manufacturers in various sizes. The most popular example being “Verivide”. To reduce the subjective element of visual colour assessment, the viewing environment must be controlled.

All fabric light box or textile light box must be fitted with the following light sources:

  • D65     – Artificial Daylight (e.g. Verivide F20 T12/D65 BS 950 Pt.1, Philips
  • MCFE 20W/84)
  • TL84   – Store Light
  • F          – Tungsten Filament (Illuminant A) (e.g. GE 40W Opal)
  • UV      – Ultra Violet Light “Blacklamp” (e.g. Sylvania F20 T12/BLB)

Application of Textile Light Box

  • Textile Light Box which use filters to provide light source should not be used. The following maintenance requirements must be observed:
  • The tubes must be replaced after 2000 hours of use and should be cleaned frequently. Please keep a record of all replacement dates and check the counter regularly.
  • Cabinets must be kept clean, in good repair and free of non-essential items such as documents and fabric samples.
  • The cabinet must be painted regularly (at least annually) internally with “Crown Colour Plan 14.40D Munsell N6.5”
  • Cabinets must be positioned to avoid ingress of direct outside light into the cabinet. Alternatively the cabinet front may be surrounded by a black curtain to block out stray light.
  • An alternative to the cabinet could be a purpose built room, which totally blocks out outside light, is lit with the correct light sources to an adequate level, is completely painted with the correct colour and is kept free of non-essential items.

Guideline for Fabric Light Box or Textile Light Box

For all orders please follow the below guideline:

  • You need a close colour match in D65 and a reasonable match in TL84. (D65 is the most important light source for checking). Both light sources must be used separately.
  • The Tungsten light (F) should be used to check for colour flaring, this is particularly important for colours made from yellow and red dye. The UV light is used to pick up the presence of optical brightening agents and          fluorescent dyestuffs and is particularly useful for checking whites.
  • Only one light source should be used at any given time, it is not acceptable to use two different light sources simultaneously.

Example of Spectra Light III Color Viewing Booth, Type D412F

The Spectra Light color viewing booth uses our patented filtered tungsten halogen light source to give you the world’s most accurate simulation of natural daylight.  It features six different levels of lighting:  Daylight (D75, D65 or D50), Illuminant A (home lighting), Horizon, Ultraviolet, and dual fluorescent sources (choice of Cool White Fluorescent, TL84 or U30).  SpectraLight features SmartLogic technology for accelerated throughput with faster color approvals.  Using the booth’s digital display, you can easily program a sequence of different light sources for hands-free viewing, maximizing operator efficiency and productivity.

Specification of lab light box 1

  • Model– light source
  • Brand: Tilo, Origin: China
  • Light Source: na
  • D-65 ( Verivide UK)    :  na or  01 set
  • TL-84 Verivide, UK      :   na or 01  set
  • CWF    Sylvania  :    01 set
  • Inca A  Crompton, UK      :    na or 01 set
  • UV  Sylvania                 :    na or 01 set
  • TL-83   Philips, Holland    :    01 set

D65 international standard artificial daylight(Artificial Daylight)
Color temperature: 6500K Power: 18WTL84 Europe, Japan, China store light
Color temperature: 4000K Power: 18WF family hotel lights, color reference light source
Color temperature: 2700K Power: 40WUV-UV light source (Ultra-Violet)
Wavelength: 365nm
Power: 18W

Specification of lab light box 2

  • Model- CAC 60
  • Fitted with below light options
  • D65 ~ Artificial Daylight
  • TL84 ~ 840P15
  • F ~ Tungsten Filament Light
  • UV ~ Ultra Violet Light
  • Interior Color-Grey 5574
  • Brand: Verivide, Origin: UK.

Maintenance of light box (Lamp Change)

Light box: The light box must have neutral grey walls with a  non-shiny surface on the inside. The grey tone should be similar to Munsell N7, N5 or Grey 5574(previously called matt emulsion smokey pine 14-40d).

To reduce the subjective element of visual colour assessment, the viewing environment must be controlled.

A standardized lighting cabinet is used for visual assessments to maintain consistency in light source, viewing area and presentation of sample.

Buyer Wise:

H&M: The lamps should be changed after 1300 hours use or after 12 months, whichever is the sooner.

TESCO: Only use lamps supplied by the original manufacturer. Replace the lamps according to the user’s manual or every 4000 hours. Service/calibrate the cabinet on an annual basis and keep a service log for future inspection.

M&S:  All Tubes or bulbs, except ultra violet tubes, must be replaced after 2000 hours or six month, whichever is the sooner.

Auto: The lamps should be changed after 1300 hours use or after 12 months, whichever is the sooner if needed.

  • Visual Assessment – All Lab Dips & Non-Accredited Suppliers
  • Lighting Cabinets and Standard Illuminants
  • To reduce the subjective element of visual colour assessment, the viewing
  • environment must be controlled.
  • A standardised lighting cabinet is used for visual assessments to maintain
  • consistency in light source, viewing area and presentation of sample.
  • The following cabinets are approved by TESCO:
  • Verivide CAC60, CAC120 or CAC150
  • Datacolor CMB Color Matcher 2028 / 2540
  • Gretag Macbeth Spectralight 111
  • Only use lamps supplied by the original manufacturer. Replace the lamps
  • according to the user’s manual or every 4000 hours. Service/calibrate the
  • cabinet on an annual basis and keep a service log for future inspection.
  • The required light sources for TESCO are as follows:
  • Light Source Use For Required Result
  • Primary Light Source D65
  • Artificial Daylight
  • All swatches Good match
  • Secondary Light Source TL84
  • General Store Light
  • All swatches Good match
  • For Checking only Tungsten (F)
  • General Domestic Light
  • To check colour constancy Do not use for
  • matching
  • For Checking only Ultra Violet (UV) To check for Optical
  • Brighteners/Fluorescent dyes
  • Do not use for
  • Matching

 GUIDELINE TO USING THE LIGHT CABINET (LIGHT BOX)

 All shade assessment and colour matching must be carried out in a purpose built colour matching cabinet (light box), which can be purchased from several manufacturers in various sizes. The most popular example being “Verivide”.

All cabinets must be fitted with the following light sources:

  • D65 – Artificial Daylight (e.g. Verivide F20 T12/D65 BS 950 Pt.1, Philips

MCFE 20W/84)

  • TL84 – Store Light
  • F      – Tungsten Filament (Illuminant A) (e.g. GE 40W Opal)
  • UV   – Ultra Violet Light “Blacklamp” (e.g. Sylvania F20 T12/BLB)

Cabinets which use filters to provide light source should not be used.

The following maintenance requirements must be observed:

  • The tubes must be replaced after 2000 hours of use and should be cleaned frequently. Please keep a record of all replacement dates and check the counter regularly.
  • Cabinets must be kept clean, in good repair and free of non-essential items such as documents and fabric samples.
  • The cabinet must be painted regularly (at least annually) internally with “Crown Colour Plan 14.40D Munsell N6.5”
  • Cabinets must be positioned to avoid ingress of direct outside light into the cabinet. Alternatively the cabinet front may be surrounded by a black curtain to block out stray light.
  • An alternative to the cabinet could be a purpose built room, which totally blocks out outside light, is lit with the correct light sources to an adequate level, is completely painted with the correct colour and is kept free of non-essential items.

For all orders please follow the below guideline:

You need a close colour match in D65 and a reasonable match in TL84. (D65 is the most important light source for checking).

Both light sources must be used separately.

The Tungsten light (F) should be used to check for colour flaring, this is particularly important for colours made from yellow and red dye.

The UV light is used to pick up the presence of optical brightening agents and       fluorescent dyestuffs and is particularly useful for checking whites.

Only one light source should be used at any given time, it is not acceptable to use two different light sources simultaneously.

Colour samples should not look noticeably different in different lights.

For further guidelines on how to assess colour and shading please see the Buyer Fabric Inspection Guideline.

Examplor of Color Matching Light Box 

Viewing cavity of color matching light box is 1260mm wide x 545mm high x 590 deep, with membrane switch panel, hour meter and electronic ballast control. Specify lamp configuration from catalog. Colour samples should not look noticeably different in different lights. For further guidelines for color matching light box on how to assess colour and shading please see more about Fabric Light Box or Textile Light Box.

Muhammad Farayaz, Lab Technologist, Amnist Textile Group of Company, Eygpt
Specification of lab light box
What is Linen Washing Machine?

What is Linen Washing Machine?

Linen Washing Machine

Linen Washing Machine is automatic machine , just have one function: cloth washing. Linen Washing Machine usually use together with TL hydro extractor for dehydration and series industrial drying machine . The linen machine adopts horizontal and drum-type structure. Linen mc has advantages of new pattern, reasonable structure, easy operation and long-life service.

Working instruction of Linen Washing MachineLinen Pre-Treatment Process

BuyerAbc buyer . 
Ref #Linen mc. 
StyleMen’s short sleeve b/d collar shirt. 
QuantityFollow  the  order  sheet , plus/ minus quantity = 5 %. 
DeliveryT.b.c 
Fabric65%linen 35% cotton. (solid & print) 
Inter liningPaper fused at collar,band & front  placket. 
Main labelSpring  field att  at   yoke  inside   2 cm  below  fm   band  edge  (4 side sts) . 
SizeWith  in  main  label  . 
Fit label“ regular fit ” att at 5 mm below from main label.

 

( 2 side sts).

 
Extra  labelN/a. 
Care  labelAtt  at  l.h. S  seam  12  cm up fm btm hem

 

(as  sample) ,

 
Button(4 hole  )14/l collar b/d = 2 pcs, 18/l neck= 1 pce, front= 6 pcs.

 

(as sample)

 
Spare btnAtt at lower  in   side   18/l 1 pce & 14/l 1pce. 18/l 5 cm & 14/l 3.5 cm up fm  btm  hem. 
 
CuffN/a 
Collar stayN/a . 
CollarHidden b/down collar (single  layer) .band inside & b/d loop cotrast fab. 
Front3 cm  rolling with 3 cm  pointed facing.( as sample). Emb at  left chest.(as worn). 
Back 2 pleat at back. Pleat depth 5mm.( as sample). 
YokeDouble. 
PocketN/a. 

Working instruction of Linen Washing Machine 1

Short sleeve3 cm width  5mm welted kansai  b4 side seam.
Lower2.5  cm  rolling. ( as sample).
Hem6 mm tail  btm .
PackStand up pack.
Neck boardUse.
Collar insertUse.
Butter flyUse.
Clip 4 pcs metal clip (logo).
PinN/a .
TissueUse –2 pcs .
Back board size.1 pce.
Folding sizeTbc.
Cuff  presentationShow.

Demirilization

  • Invatex CRA=0.5 g/l
  • Invatex CS=0.5g/l
  • 80OCX10`
  • Albafluid –C=1.0 g/l
  • Invatex CRA=0.6 /l
  • Amplex DS=05 g/l
  • Albaflow JET=0.05 g/l
  • Reduzin OS=1.0 g/l
  • NaOH=2.5 g/l
  • H2O2= 8.0 g/l
  • 980CX20`

Shrinkage:

Knitted fabric tends to change dimensions in length and width after being taken off the machine. The more favorable conditions for fabric’s relaxation provided during washing. Change of dimensions after knitting can create major problem in garments and fabrics especially. Those produce from hydrophilic fibers such as wool and cotton. Knitting from

Thermoplastic fiber and synthetic fibers such as nylon and polyester can be heat set to shape or to dimensions that are retained unless the setting conditions are exceeded during washing and wearing.

Alkylphenols (APs) and Alkylphenol Ethoxylates (APEOs)

Alkylphenol Ethoxylates are considered to be harmful and toxic to the environment and possible endocrine disrupters. The most common usage is in detergent products and emulsifying agents. The second most common use is in textile processing (in particular with fibres such as linen and silk, whose naturally occurring gums and resins make them difficult to wet out) where it is used in various textiles auxiliaries including wetting agents and in the manufacture of water based pigment pastes to improve pigment dispersion.

The use of APs and APEOs specifically containing Octyl Phenols (OP) & Nonylphenols is restricted in all areas of David Howard production.

Nonylphenol Ethoxylate (NPEO), Octylphenol and their Ethoxylates (Alkyl Ethoxylates)

David Howard do not accept the use of any of the above chemicals in the production or processing of our goods.

APPEARANCE AFTER WASH

This method has been developed as there are no national or international standards based on this method at the present time.

SCOPE

To determine the degree of appearance retention after machine washing.

PRINCIPLE

A finished/completed garment is washed and assessed against an unwashed garment for deterioration in appearance.

APPARATUS

  1. Automatic washing machine as specified in BS EN 26330:1994
  2. Commercially available detergent
  3. Grey scales for assessing change in colour as BS EN 20105 A2
  4. Veri-vide light cabinet (or equivalent) with lectern
  5. Drying facilities as applicable to garment care label, flat or hang or tumble dryer as             specified in BS EN 26330:1994

CONDITIONING & TESTING ATMOSPHERE

It is not necessary to condition samples nor carry out the testing or assessment in a standard atmosphere. Ordinary room conditions are satisfactory provided the correct procedure is followed.

TEST SPECIMENS

Minimum of two finished/complete garments

PROCEDURE

Make wash load up to 2kg

  1. Place one garment in the washing machine
  2. Add detergent, sufficient to give 3cm running suds and sodium perborate (ECE detergent to be used at a ratio of 4:1 with sodium perborate).
  1. Run the machine (select programme to match garment care label).
  2. Dry according the garment care label instructions
  3. Compare the washed specimen with the unwashed duplicate in the light cabinet             under artificial daylight D65.

RESULTS

Assess garment for cross staining using grey scales

Assess garment for shade change using grey scales

Assess the appearance of the garment for the following areas:

Creasing of Garment

(If creasing is evident, iron to care label and re-assess garment)

Differential Shrinkage within garment

Distortion of garment around attached components (e.g. Zips)

Distortion of garment around embelishment (e.g. Embroidery)

Deterioration of trims

Breakage or distortion of seams

Skewing of the garment

Overall appearance of the garment – Satisfactory or Unsatisfactory

REPORT

Grades for Cross Staining & Colour Loss

Visual observations on change in garment appearance as outlined above.

Special instruction of Linen Washing Machine

  • Wash : gmts wash with softner.
  • iron : no iron only steam.
  • lining colour : white.
  • inter lining  art no : 6050 for collar, band & f/plkt facing. (s/cut) .
  • s.p.i – 12/13.
  • contrast : printed contrast fab use at collar b/d loop & inside band.
  • Edge stitch at collar joint, band joint,collar b/d loop & f/plkt faching.
  • 5mm top sts at collar,f/shoulder & back yoke.
  • 6 mm frence  seam  at armhole .
  • btn st colour: contrast.
  • Side seam  feed of the arm both side at front,   st to st gap 6mm .
  • Hole  measurement: neck  seam to 1st  hole  5.5 cm   restof hole 9.5 cm  .
  • btn att thread cross & lock stc.
  • collar point        –    6 cm.
  • collar height    –     4 cm.
  • band height        –     3 cm.
  • collar space       –     1 cm.
  • collar spread    –     7 cm.
  • hang tag  &  fitting  tag  att. At body 1st btn with string .
  • round  size  sticker  att. At  poly top  (l.h.s)1″ fm edge  & bottom  (r.h.s) 1″ fm edge .   ffff
  • long  size  sticker : inside of collar insert of linen washing machine
All Generator List and Standard Operating Procedure

All Generator List and Standard Operating Procedure

Generator List

The objective of this Standard Operating Procedure is to describe the procedure for operating the Diesel Generator of Engineering department of Auto Generator Medicine Ltd. This procedure is applicable for operating Diesel Generator under engineering department of Auto Medicine Ltd. Area of operation is Service Building under engineering department. The content lists are –

What is Servo Motor? How Servo Motors Work?

Led Work Light for Sewing Machine

What is Electrical Safety Training System ?

SOP for Electrical Management and Maintenance

What is Generator Cooling Tank Chemical Process?

Diesel Generator Maintenance Check List

Gas and Diesel Generator Maintenance Cost

Gas and Diesel Generator Maintenance Cost

Gas and Diesel Generator Maintenance Checklist

Responsibility

Operators under engineering department are responsible for following this SOP.

Routine responsibility for ensuring that this procedure is implemented as and where necessary rests with the Head of Engineering department.

Quality Assurance Department is responsible for SOP compliance.

Involved

All concern Operators, Executives / Officers and Head of Engineering Department.

Definition & Abbreviation 

Definition: There is (are) no unique term(s) in this document.

Abbreviation: There is (are) no unique term(s) in this document.

Health &  Safety Consideration

Wear sound & Eye protective devices during machine operation.

System / Process Owner

Engineering Department

Description & Specification Of Machine

Manufacturer: Auto Engineering Co. Ltd. Model: WPS400: Supplier :Sim Power, Machine No: 0174707/012&015, Material: All  parts are made of MS Metal with paint. Generator Details: 3 Phase,415V, 50Hz.1500 RPM Capacity: 400KVA each

Procedure

Preoperational  Steps

At first check & certify that the machine is workable & ready for operation

Check the oil level. The pointer should register in the upper field of the green range. If the pointer registers in the red range (Low range), Remove the plug & add oil until the level reaches the filter        opening. Fit & tighten the plug.  Check the radiator water level .  Check the Lub oil level & Quality. Check the Battery Voltage 24 Volt

Operational Steps

Staring

Switch on the Generator Display in Manual Mode, then Press ‘Start’

Run the Generator Set for Minimum Two minutes

Switch on the Generator panel ACB

Select Synchronizing panel in Auto/Manual Mode)

Switch on the LT-2 ACB

Switch on the BBT ACB

Stopping

Switch off the BBT ACB

Switch off the LT-2 ACB

Switch off the Generator ACB, Press ’O’

Run the Generator for five minutes with out load(No load)

At the end of operation, switch off the Generator Off Push.

Caution

During operation, if any unusual or abnormal sound or noise is heard or problem arises, stop the machine immediately and inform it to the Engineering in charge.

Before carrying out any maintenance, repair or adjustment, stop the Generator, Press emergency stop button, switch off the ACB.

Post operational steps

Check the Generator Voltage, 400Volt AC.

Check the running Ampere

Check the Generator Temperature,80-10c

Check the Generator Oil Pressure,70-100 psi

Check the Generator Frequency,50Hz

Check the Generator RPM,1500 rpm

Record the Generator running hour reading

Special Instruction

Should there be anything in this SOP that you do not clearly understand or cannot implement, please communicate it immediately to your superior officer.

Review / Change History                               

The procedure must be re-prepared, checked and duly approved whenever any change in the system/   method/ process, or in any circumstance, indicates the need for the same.

The SOP must be reviewed every 3 (three) years from the date of issue, in the light of current practice, to determine whether any change or revision is necessary.

All copies of the SOP which will be superseded by any revision must be withdrawn from active use.

After recalling all the copies of the superseded SOPs, redistribute the reviewed one by keeping records in Log books.

Preserve a copy of the superseded SOP in document archive and destroy rest of the copies keeping records.

Example of Costing for Utility and Maintenance Section

   Generator Costing:

  • Total Cost per Year for Generator = 2, 244545, 45,328 Tk.
  • Total Cost per Month for Generator = 18, 74540,444 Tk.
  • Total Cost per Day for Generator = 61,4945454 Tk.
  • Total Cost per Hour for Generator = 2,554562 Tk.
  • Per KW Electricity Cost = 2.74548 Tk.

Boiler Costing:

  • Total Cost per Year for Boiler = 1, 87, 04542,744 Tk.
  • Total Cost per Month for Boiler = 15, 58,5454562 Tk.
  • Total Cost per Day for Boiler = 51,254540 Tk.
  • Total Cost per Hour for Boiler = 2,1345455 Tk.
  • Per Kg Steam Cost = 0.145457 Tk.

Compressor Costing:

  • Total Cost per Year for Compressors = 31, 514545,908 Tk.
  • Total Cost per Month for Compressors = 2, 624545,659 Tk.
  • Total Cost per Day for Compressors = 8,635455 Tk.
  • Total Cost per Hour for Compressors = 3454560 Tk.
  • Per m3 Air Cost = 0.35453 Tk.

E.T.P Costing:

  • Total Cost per Year for E.T.P = 1, 36, 67,5645458 Tk.
  • Total Cost per Month for E.T.P = 11, 38,954564 Tk.
  • Total Cost per Day for E.T.P = 37,4565645.39 Tk.
  • Total Cost per Hour for E.T.P = 1,565e6560.22 Tk.
  • Per m3 Water cost for E.T.P = 1667676.95 Tk.

W.T.P Costing:

  • Total Cost per Year for W.T.P = 43, 67,46767684 Tk.
  • Total Cost per Month for W.T.P = 3, 63,56565957 Tk.
  • Total Cost per Day for W.T.P = 11,96565656 Tk.
  • Total Cost per Hour for W.T.P = 4994545 Tk.
  • Per m3 Water Cost for W.T.P = 5.23434 Tk.
  • Per m3 Water Cost for Washing = 1.34342 Tk

MAINTENANCE TOTAL COSTING

  • Total Maintenance cost = 2,22329,95,642 Taka
  • Total Maintenance cost per month = 19, 16,3232304 Taka
  • Total Maintenance cost per day =63,8232377 Taka
  • Total Maintenance cost per hour =2,623262 Taka

MAINTENANCE TOTAL COSTING

  • Total Maintenance cost per day =98,732300 Taka
  • Total Maintenance cost per month = 223239, 60,971
  • Total Maintenance cost per Hour =4,113233 Taka                                                                                                                                                                                        

MAINTENANCE TOTAL COSTING SUMMARY

  • Total Maintenance cost in 2011 = 3,07,98323,474 Taka
  • Total Maintenance cost per month = 25, 623236,540 Taka
  • Total Maintenance cost per day =85,552321 Taka
  • Total Maintenance cost per Hour =3,532365 Taka

MAINTENANCE TOTAL COSTING SUMMAR

  • Total Maintenance cost in 2012 = 5,73,91,632367 Taka
  • Total Maintenance cost per month = 47, 82,632339 Taka
  • Total Maintenance cost per day = 1, 59,423231 Taka
  • Total Maintenance cost per Hour = 6,643233 Taka
Gas and Diesel Generator Maintenance Checklist

Gas and Diesel Generator Maintenance Checklist

Gas and Diesel Generator Maintenance Checklist 

In order to meet gas and diesel generator maintenance to growth of production and extension of the project we immediate need the bigger capacity of Power Gas Generator Unit. This is why we are interested to improve the 900KW/1125 KVA Gas Generator.

Panel – Gas and Diesel Generator Maintenance Checklist 

  • Adequate illumination available infront of DB?
  • Is panel board at accessible height?
  • Are Instruction Board (both) displayed on the DB?
  • Electric Danger/Caution sign available on the panel?
  • Are indicator lamps available and functional?
  • Are Ammeters (for LT & MDB) available?
  • Are Voltmeter (for LT & MDB) available?
  • List and diagram (SLD) of circuits available?
  • Notice for periodic inspection and testing (at LT) available?
  • Are means for identification available for the final circuits?
  • Are the no. of outgoing Circuit Neutral conductors equal to the no. of outgoing Circuits?
  • Are means for identification available for Circuit-Neutral conductors?
  • Are the no. of outgoing Circuit Earthing conductors equal to the no. of outgoing circuits?
  • Are means for identification available for all of circuits?
  • Is there any means inside panel to prevent excessive protective devices?
  • Are Phase bus-bars used in the panel?
  • Is Neutral bus-bar used in the panel?
  • Is Earth Bus-bar used in the panel?
  • Is Earth Bus-bar properly connected with the loads?
  • Are all Phase conductors following colour code?
  • Are all Neutral conductors following colour code?
  • Are all Earth conductors following colour code?
  • Are Neutral and Earth Bus-bar shorted?
  • Is the Panel Body connected with ECC?
  • Is the Panel Door connected with ECC?
  • Rubber/Insulating mat available infront of boards?
  • If available, adequate?
  • If available, graded?
  • Proper bushing/glands for incoming and outgoing cables available?
  • Interlocks provided for multiple power sources (LT & MDB)?
  • Is the main incomer of the panel is operable?

Generator Room – Gas and Diesel Generator Maintenance Checklist 

  • No/Insufficient /Unsafe stair at the entrance of the Generator room is it true?
  • Is Combustible material in the Generator room?
  • Is Rains water enters into the generator room
  • No/insufficient lighting inside the generator room?
  • Are Lints/dirts present in the Generator room?
  • Are Combustible Materials in cable trench ?
  • No Cover on cable trench, is it true?
  • Improper Installation of LT meter, is it true?
  • Generator frame earthing not done, is it true?
  • Generator frame earthing done partially (One instead two), is it true?
  • Is Battery terminal is open?
  • Top and bottom of the generator supply terminal box open, is it true?
  • Generator supply terminal box not staled, is it true?

Substation Room- Gas and Diesel Generator Maintenance Checklist 

  • No/Insufficient /Unsafe stair at the entrance of the Substation room, is it true?
  • Is Combustible material in the /Substation room?
  • Is Combustible material near the HT?
  • Is Rains water enters into the substation room?
  • No/insufficient lighting inside the Substation room ?
  • Are Lints/dirts present in the Substation room?
  • Are Combustible Materials in cable trench?
  • No Cover on cable trench, is it true?
  • Improper Installation of LT meter, is it true?
  • Transformer
  • X-former installed on combustible wooden stick,is it true?
  • Horn gape Upper/lower part missing, is it true?
  • Horn gape not aligned, is it true?
  • Is Silica gel of x-former breather becomes brown?
  • Transformer Breather oil pot empty, is it true?
  • Equipment -earthing and systemearthing shorted?
  • Huge dirt present on the top and at the bottom of the transformer
  • Huge dirt present in the transformer area?
  • Earthing connected with x-former body w/o lug

Spear Parts Air Compresor Ceccato

1) Oil Separator Kit

2) Oil Stop Kit

3) Cheek Valve Kit

4) Mini Pressure Valve Kit

5) Thermostatic Valve Kit

6) Pressure Switch – 600657.

7) Solenoid Valve – 599949

Temperature Meter – 600626

Thermo Switch

Piston for Minimum Valve

Seal for minimum Valve

U4 Valve

Pressure Regulator

Spear Parts For All Motor Pump:

  • Coupling Rubber Bush – As Per Sample.
  • Magnetic Contactor – As Per Sample.(Control Volt 220V.)
  • Timer – As Per Sample.
  • Pressure Controller Switch – As Per Sample.
  • Really – As Per Sample.
  • Pressure Gauge – As Per Sample.

Spear Parts Caterpillar Generator

  • Spark Plug – 2N – 2839 – Caterpillar.
  • Wire A – 7W – 8542.
  • Oil Filter – IR – 0716.
  • Filter Shoot – 8N – 2555.
  • Element Air – 8N – 6309.
  • Indicator Assay – 3E – 7238.
  • NGEO (Mobil) – EL 250 SAE 40. (Change After: 1200 Hours)
  • Lubricant (Grease) – 2S – 3230.

Spear Parts Petbow Generator

  • Air Filter – AF – 928 M.
  • Water Filter – WF – 2075.
  • Fuel Filter – FS – 1212.
  • Lube Oil Filter – LF – 3000.
  • Diesel
  • Mobil – SAE – 40.

Conclusion

We have significantly increased the production capacity by commissioning the new set of fully Gas and Diesel Generator Maintenance and Semi Auto corrugated board making machine. In addition to this we have added two color Offset printing machinery in our offset printing section. Also turning the offset printing Floor Air condition to meet buyer’s demand. Further, to meet the quality product we will have to commission high capacity Boiler. Know more about Diesel Generator Maintenance Checklist and cost.

Gas and Diesel Generator Maintenance Cost

Gas and Diesel Generator Maintenance Cost

Generator Maintenance

I would like to inform you the diesel generator maintenance cost , from the very beginning we found, our Generator has created too much high temperature. Some times Generator has shut off. For that reason, we informed your Engineers to solve this problem but they are unavailing to find out the problem and solve it. Several times our production has hampered. In front of your Engineers we have opened our Generator Heat Exchanger and we’ve found a big size (2.2”X2.2”) round metal pc. GETCO Engineer also agrees with us that this is the main problem for high temperature and also manufacturing fault.

 Generator Maintenance Proposal

 With due respect would like to inform you that our Generator (GAS) have to servicing after every 1000 hours and also lube oil change. For this reason in next Friday January 21, 2010. from 01.00 pm. to 7.00 pm. want to set for servicing the Generator.  So, with beg most respectfully that you will give the permission for servicing the Generator on the above date and time.

 Materials/Spare Parts Rate For Gas Generator:

S/L No.

 

 

Description Of The Materials/ Spare Parts Qty

 

 

Rate (Tk.)

 

 

01Generator Total Price02 Pieces4,00,00,000
02Engine Oil01 Liter425
03Oil Filter01 Piece3,300
04Air Filter01  Piece10,500
05Air Filter Shoot01 Piece1,300
06Spark Plug01 Piece7,433
07C.W.T-51201 Kg330
08C.W.T-51301 Kg352
09Coolant/Additive01 Liter990
10Gas Bill01 Month8,50,000
11Over Hauling Cost 5,00,000
12Other Servicing Cost01 Month5,000

 Life Time = 15 Years

= (15×12) Months

= 180 Months

 Generator Maintenance Cost

S/L No.Description Of The Materials/ Spare PartsQtyRate (Tk.)Total (Tk.)
01Generator Price02 Pieces(2×2,00,00,000÷180)2,22,222
02Back-Up Oil338 Liters4251,43,650
03Changed Oil208 Liters42588,400
04Oil Filter1.5 Pieces3,3004,950
05Air Filter1.25 Pieces10,50013,125
06Air Filter Shoot1.25 Pieces1,3001,625
07Spark Plug3.33 Pieces7,43324,752
08C.W.T-51210 Kg3303,300
09C.W.T-51310 Kg3523,520
10Coolant/Additive10 Liters9909,900
11Gas Bill01 Month8,50,0008,50,000
12Over Hauling Cost  5,00,000
13Other Servicing Cost01 Month5,0005,000
   Total=18,70,444
  • Total Cost per Month for Generator = 18, 70,444 Tk.
  • Total Cost per Year for Generator = (18, 70,444×12) Tk. = 2, 24, 45,328 Tk.
  • Total Cost per Day for Generator = (2, 24, 45,328÷365) Tk. = 61,494 Tk.
  • Total Cost per Hour for Generator = (61,494÷24) Tk. = 2,562 Tk.

Generation Per Day (Average):

  • Old Caterpillar Gas Generator = 12 MW
  • New Caterpillar Gas Generator = 12 MW
  • Total Generation per Day = (12+12) MW

= 24 MW

= (24×1,000) KW

= 24,000 KW

  • Total Generation per Month = (24,000×28) KW

= 6, 72,000 KW

  • Per KWH Cost = (18, 70,444÷6, 72,000) Tk.

= 2.78 Tk.

Load Calculation For All Units (Average)

Units NameAmp.KWHRate/KW (Tk.)Total Cost (Tk.)
Textile4782652.78736.70
Generator Room70392.78108.42
Utility (Boiler Room)5603102.78861.80
Washing158882.78244.64
E.T.P-2160892.78247.42
Knitting171952.78264.10
Garments7013892.781081.42
E.T.P-1133742.78205.72
Embroidery100562.78155.68

Per Month Electricity Cost for All Units:

  • Per Day electricity cost for Textile = (736.70×24) = 17,680.80 Tk.
  • Per Month electricity cost for Textile = (17,680.80×28) = 4, 95,062.4 Tk.
  • Per Day electricity cost for Generator Room = (108.42×24) = 2,602.08 Tk.
  • Per Month electricity cost for Generator Room = (2602.08×28) = 72,858.24 Tk.
  • Per Day electricity cost for Utility (Boiler Room) = (861.80×24) = 20,683.2 Tk.
  • Per month electricity cost for Utility (Boiler Room) = (20,683.2×28) = 5, 79,129.6 Tk.
  • Per Day electricity cost for Washing = (244.64×24) = 5871.36 Tk.
  • Per Month electricity cost for Washing = (5871.36×28) = 1, 64,398.08 Tk.
  • Per Day electricity cost for E.T.P-2 = (247.42×24) = 5,938.08 Tk.
  • Per Month electricity cost for E.T.P-2 = (5,938.08×28) = 1, 66,266.24 Tk.
  • Per Day electricity cost for Knitting = (264.10×24) = 6,338.4 Tk.
  • Per Month electricity cost for Knitting = (6,338.4×28) = 1, 77,475.2 Tk.
  • Per Day electricity cost for Garments = (1081.42×24) = 25,954.08 Tk.
  • Per Month electricity cost for Garments = (25,954.08×28) = 7, 26,714.24 Tk.
  • Per Day electricity cost for E.T.P-1 = (205.72×24) = 4,937.28 Tk.
  • Per Month electricity cost for E.T.P-1 = (4,937.28×28) = 1, 38,243.84 Tk.
  • Per Day electricity cost for Embroidery = (155.68×24) =3,736.32 Tk.
  • Per Month electricity cost for Embroidery = (3,736.32×28) = 1, 04,616.96 Tk.

Generator maintenance  – Cooling Tower

  1. Ball Valve 1”
  2. Butterfly Valve 4”(with Flange)
  3. Butterfly Valve 6”(with Flange)
  4. Butterfly Valve5”(with Flange)
  5. Centrifuge High lift Pump
  • Flow rate 120M/H
  • Head 20M
  • Suction 6”
  • Delivery 5”
  1. Expunction Joint 4” (with Flange)
  2. Expunction Joint 5”(with Flange)
  3. Foot Valve 6”(Flange type, with Flange)
  4. MS Elbow 2”
  5. MS Elbow 4”
  6. MS Elbow 5”
  7. MS Elbow 6”
  8. MS Reducer 4”*2”
  9.  MS Reducer 4”*5”
  10. MS Ring Flange 4”
  11. MS Ring Flange 5”
  12. MS Ring Flange 6”
  13. MS Simless Pipe 4”
  14. MS Simless Pipe 5”
  15. MS Simless Pipe 6”
  16. MS Simless Pipe 8”
  17.  Non return Valve 5”(disk type)
  18. Nut bolt with washer (full thread) 16*120
  19. Nut bolt with washer 16*50
  20. Nut bolt with washer 16*65
  21. Nut bolt with washer 20*50
  22. Nut bolt with washer 20*50
  23. Pressure gauge
  24. Strainer 6”       (Flange type, with Flange)
  25. Temperature gauge (0-100,300)

Generator maintenance – Exhaust Gas Line

  1. MS Flange (as per sample)
  2. MS Simless Pipe 12”
  3. Temperature meter (0-500 c)

Generator maintenance – Inlet Gas Line

  1. Ball valve ½”
  2. Ball Valve 4” (Flange type)
  3. Gas Filter 4”(with Generator)
  4. MS Elbow 4”
  5. MS Flange 4”
  6. MS Pipe 4”
  7. MS Reducer ( 4”*3” welded type)
  8. Niddle valve with sypone pipe ½”
  9. Pressure gauge (0-200 PSI)
  10. PRV (Gas regulator Valve3”)
  11. S S Expansion Joint 4” (with flange)
  12. Solenoid Valve 4” (with flange) with Generator

Gas and diesel generator maintenance cost is described in this article