Fire Findings Example
Fire Findings -Are manual fire extinguishers regularly inspected and marked on tags? Do the employees know how to use fire-fighting equipment? Is the local fire department acquainted with the facility? Is workplace free of electrical / mechanical hazards? Does the facility have an adequate number of properly located and clearly marked emergency exits available? Are exits easily accessible, kept clear, and kept unlocked during working hours? Are aisles kept clear from obstructions at all times. Read more Fire Safety for Workplace of Manufacturing Company …
- During audit time it was noted Fire extinguisher user instruction missing Ground floor generator room.Maximum area floor marking found rub out and yellow color not highlighted in damp color floor. It is recommended that factory can use RED color with the yellow paint for easy understanding.
- During audit time it was noted that there is no Fire Findings extinguisher at at 8th floor It server room.Chemical/ Oil drum found stored in open area and without secondary containment. Chemical drum and Oil drum needs to use secondary containment for environmental safety. It is recommended that factory should make the separate area for oil and chemical storage under the shaded.
- Maximum area of the production floor aisle found partially/ fully blocked. It is recommended that factory should ensure all the aisles should be free form any emergency safety.
- During audit time it was found that one fire extinguisher hanging hook broken at 8th floor godown In the workers time card found inconsistency with the salary sheet which will be high risk for walmart audit. Pls make sure last one year documents should be updated for coming audit.
- During audit time Gong bell were found without rope Ground floor Fabric store. Shift wise duty some area not effected as per time card and others documents also no working hours notice found for the month of Ramadan.
- During audit tme it was noted that only auto smoke detectors base installed but auto smoke detector missing
- All the security duty roster and register should formatted as on their shift of duty.
- Maximum Electric panel board found without ebonite sheet for safety. Battery operated (battery back up) Fog light missing at 5th Floor Sewing west exit.
- Maximum area found workers are working without mask/ hand gloves/ eye guard etc as required safety hazards area.
- Available holiday records found in your poly, packaging and store area. This will be high risk violation for Walmart audit requirements. Make sure all the production record/ register and workers handout are removed from the production and storage and HR section.
- During audit time we found one fire extinguisher where there is no checklist.
- During audit time it was found that one Fire Findings extinguisher were blocked by sewing machine
- Workers final settlement record found Excessive working hour payment sheet, which will be also high risk for factory in terms of walmart Code of Conduct. Pls make sure all final settlement file should be clean without excessive work payment record.
- Some workers found who are looking younger. Pls make sure no below 18 workers are working in your factory.
- During audit time it was noted that there is no PA system at floor Newgen room. Maximum section found without Evacuation Plan mark, and some area found Evacuation plan not sufficient (Packaging area) needs more require on factory size.
- Maximum EXIT mark found missing on the Exit door and some area found only EXIT mark, it is recommended that factory should use the EXIT mark both of language (English & Bangla) in any sign/ posted notice board. Only English is not easy understanding for general workers.
- During audit time it was found that Fire hose pipe were box blocked by caring trolley at 6th Floor Cutting section. Fire equipment found not sufficient as per Fire Findings license, also required more as per floor condition. It is recommended that factory should ensure the fire equipment sufficient all the time also use more equipment because this plant is running by highly flammable particulars.
Some Recommendation
- Factory should provide a new fire extinguisher hook for said area.
- Factory HR & Compliance department should have provide fire extinguisher for said area..
- Factory should Fix up the fire alarm switch cover as early as possible.
- Factory should maintain the compliance checklist daily with effectively
- Factory should have provide fire extinguisher checklist with all Fire Findings Extinguishers .
- Factory should install Battery operated (battery back up) Fog light at said exit.
- Factory should keep always all aisle block free.
- Factory should maintain the compliance checklist daily with effectively.
- Factory should maintain the compliance checklist daily with effectively.
- Factory should maintain the compliance checklist daily with effectively.
- Factory should provide PA System over there as early as possible.
- Factory should provide rope for gong bell as early as possible.