Check List for Fire Safety Device
- Access limited or barred to DB / DB blocked
- Access limited or barred to the panel / panel blocked
- Access limited/barred to MCB/MCCB-box
- Access limited/barred to Socket. Access limited/barred to Switch-Board
- Access limited: Earth-bar not accessible inside the panel
- Air gap between phases less than 25 mm in cases of bare conductors (e.g., bus-bars)
- Ammeter / Voltmeter/indicator/PFI auto-controller not working
- Ammeter/Voltmeter’s selector switch bad
- Bunch of cable/multiple wires /looping wire connected at incomer MCCB/MCB’s input/output terminal
- Bunch of cable: looping from incomer MCCB/MCB’s input terminal
- Bunch of cable connected at bus-bar
- Bunch of cable: Multiple connections through one outlet of final-BBT
- Bunch of cable: Multiple connections ( more than two) through one socket outlet
- Burning sign on conductor at incomer MCB/MCCB’s input/output terminal
- Burning sign on conductor at the connection point to bus-bar
- Burning sign on Current Transformer inside the panel
- Burning sign on phase bus-bar, Burning sign on socket
- combustible wooden board : Use of wooden board/enclosure for MCCB/MCB
- Combustible material in the generator room
- Combustible material in the substation
- Combustible material near the HT panel/ HT line
- combustible wooden board: Tube light /Bracket Light/spot light/Normal light installed on wooden Board
- Combustible wooden board: X-former installed on combustible wooden plank
- combustible wooden board: Grinding M/C (or other M/Cs) installed on wooden platform/table/combustible material
- combustible : Light-shed tied with combustible material
- Combustible material in touch of MCB/MCCB-Box
- Combustible material in touch of Socket
- Combustible material in touch of Switch-Board
- Combustible material is used to seal the Panel Board
- Combustible material on / touching (adjacent to)/attached on the panel
- Combustible material on Cable Tray
- Combustible material on or touching (adjacent to) Cable Tray
- Combustible material in Cable Trench, Combustible material tied with/in touch of BBT
- Combustible material touching exhaust fan
- Combustible material used as support for the Cable Tray
- Combustible material used as support for the panel
- Combustible materials: Socket installed on combustible materials
- combustible wooden board: Cable channel made with combustible wooden board
- combustible wooden board: SB installed on combustible material/wooden board
- Combustible wooden board: The live parts of the panel (buses) are guarded with combustible wooden board
- Combustible material in touch of / near motor
- Combustible material in touch of/near wire/cable
- Combustible material near the Cable Tray
- Combustible material near the panel ( Just below or with in 3feet)
- Combustible material near any Electrical Apparatus
- Combustible material near BBT, Combustible material near IPS-Unit
- Combustible material near Light-shed
- Combustible material near MCCB/MCB-box
- Combustible material near Switch-Board
- Combustible material near/surrounding Socket
- Combustible material used as support for any installation
- Combustible material: IPS-Unit kept on combustible material
- Earth-bar shorted with neutral-bar
- Earthing cable not connected properly at the panel door
- Earthing: One point frame earthing of the generator instead of two
- Flexible cord’s outer insulation discontinued
- Lint/dirt present in the transformer area
- Lint/dirt present on the top and at the bottom of the transformer
- Lint/dirt: Lint/dirt present in the S/S or generator room
- Lint/dirt present in the S/S room
- lint/ dirt, spider-net or combustible material present inside the panel board
- Improper installation of light sheds
- Improper installation of MCB/MCCB
- Improper installation of socket
- Improper installation:-Cable laying on the Cable Tray improperly
- Improper installation:-Ceiling fan blade at accessible height
- Improper installation:-Chemical stored inside the maintenance room without any proper separator.
- Improper installation:-DB installed at a height out of normal reach
- Improper installation:-DB installed in the chemical room / chemical store
- Improper installation:-Empty earth-bar
- Improper installation:-Empty neutral-bar
- Improper installation:-Equipment-earthing and system-earthing shorted
- Improper installation: Extension line taken from ceiling rose point instead of socket outlet.
- Improper installation:-Lamp holder at an accessible height & without any lamp
- Improper installation:-MCB/MCCB installed without enclosur
- Improper installation:-Neutral & earthing of transformer are connected at the same point
- Improper installation: No neutral-bar at all
- Improper installation:-Normal light (uncovered) above combustible materials
- Improper installation:-Normal light above combustible materials or chemical in store
- Improper installation:-Normal Socket installed in the chemical room /chemical store
- Improper installation:-Normal Switch Board installed in the chemical room / chemical store
- Improper installation:-Pump/Motor base not made properly
- Improper installation:-Pump/Motor not fixed with base properly
- Improper installation:-SB installed at an inaccessible height
- Improper installation:-Scotch tape used to tie wires inside the panel board instead of cable tie.
- Improper installation:-Cable conduit on wall not clipped properly
- Improper installation:-Rod-gap not aligned
- Improper installation:-Indicators not in proper sequence (R-Y-B)
- Improper installation:-No cover on cable trench specially in sub-station and generator room.
- Improper installation:-Undressed messy wire present inside the panel.
- Improper installation:-Undressed power electrical conduits.
- Improper installation:-Wiring channel under the table
- Lighting: No/insufficient light on working platform in the maintenance room
- Lighting: No/insufficient lighting inside the S/S or generator room
- Loose:-Bracket light holder loos
- Loose:-Ceiling rose loose
- Loose:-Light shed loo
- Loose:-MCB/MCCB-box loose / broken / not sealed
- Loose:-Socket loose / broken / not sealed
- Loose:-Tube light guard loosens and tied with copper-wire
- Mechanical guard :-No/ broken /discontinued /insufficient mechanical guard on power cable at wall/floor
- Mechanical guard :-No/ broken /discontinued /insufficient mechanical guard on wiring cable
- Missing: Horn-gap upper/lower part missing
- Missing: Bracket light cover missing
- Missing: Silica gel of x-former breather becomes brown
- Missing: Transformer breathers oil pot em
- No earthing connection at electric iron (if metal body)
- No earthing connection at spot removing spray gun
- No ECC:-Motor ECC not done
- No frame earthing at generator
- No earth bus-bar at all
- No earthing connection at any rotating M/C
- No earthing connection at auto shaker M/C at lab
- No earthing connection at cad tester M/C at lab
- No earthing connection at fridg
- No earthing connection at grinding M/C
- No earthing connection at kettle
- No earthing connection at Socket
- No earthing connection at the welding M/C
- No earthing connection at the welding M/C (or other M/C)
- No ECC at any electric equipment
- No ECC:-at IP
- No ECC:-Cable armor not connected with the ECC
- No ECC: Pump suction and delivery pipe ECC not done
- Inadequate ECC at electrical equipment/Panel/ Motor
- No earthing connection at the panel door
- No ECC:-Cable channel body earthing not done
- No ECC:-Cable trunking body earthing not done
- No/insufficient/incomplete lightning protection
- No/insufficient/unsafe stair at the entrance of the substation
- No/insufficient/unsafe stair to the entrance of lift room
- Not sealed:-BBT end cover missing
- Not sealed: Drill M/C (or other M/C’s) connection terminal not sealed properly
- Not sealed: Generator’s supply terminal box not sealed
- Not sealed: Motor connection terminal cover not sealed / glanded
- Not sealed:-No cover is used over ceiling rose
- Not sealed: Pump/Motor connection terminal cover not sealed / glanded properly
- Not sealed:-Top-Bottom of Energy meter Box/Enclosure open (not sealed)
- Not sealed:-Bottom of the panel (cable entry-exit point) is open
- Not sealed:-Panel door not sealed properly
- Not sealed:-Switch-Board loose / broken / not sealed
- Not sealed:-Tap-off box not sealed
- Not sealed:-The changeover switch enclosure not sealed
- Not sealed:-The Panel board not sealed
- Not sealed:-Top and bottom of the generator’s supply terminal box open
- Not sealed:-Top of the panel (cable entry-exit point) is open
- Not sealed: Circular Box cover broken
- Not sealed: Circular Box without cover
- Not sealed: No bush / gland at the cable entry-exit point
- Nut-bolt-washer for electrical connection rusted
- Panel door: Door lock bad
- Panel door:Panel door-hinge broken
- Panel door:Panel door cannot be closed fully
- Panel door:Panel door cannot be opened fully
- Panel door: Panel cover is fixed by nut-bolt
- Panel door:Panel door is locked by pad-lock
- Protection: Bypassing the Fuse
- Protection: Bypassing the incomer MCBB/MCB
- Protection: Bypassing the MCBB/MCB
- Protection: MCCB/MCB’s knob broken
- Protection: The incomer MCCB/MCB’s knob broken
- protection: Lines taken for indicators/Voltmeter/Ammeter w/o fuse or MCB
- Rubber mat ;-No rubber mat in front of the panel
- Rubber mat ;-Non-graded rubber mat in front of the panel
- separator :One slot left without phase separator at incomer MCCB’s input /output terminal
- separator: No/insufficient phase separator at incomer MCCB’s output terminal
- separator: No/insufficient phase separator at the MCCB’s input terminal
- Splicing / improper cable joint at the same point of both phase and neutral conductors
- Splicing / improper cable joint at the same point of both phase conductor and ECC
- Splicing / improper cable joint at the same point of both phases
- Splicing joint used instead of using earth-bar
- Splicing joint: No ceiling rose used to connect the tube light /tube light shed (connected by splicing joint)
- Splicing joint on cable inside Cable Channel without PIB tape
- Splicing joint: Exhaust fan connection through no outlet (connected by splicing joint)
- Splicing joint: Splicing at earthing bar
- Terminal open:-Battery terminal is open
- Terminal open:-Generator self starter’s connection terminal open
- Terminal open:-IPS-battery terminal open
- Unterminated /exposed wire/exposed conductor/exposed bus-bar end (live/dead) inside the panel
- Unterminated/open/exposed wire (live/dead) throughout the factory.
- W/O Lug: Connection at incomer MCCB’s input / Output terminal w/o lug
- W/O Lug: Connection without lug at phase bus-bar
- W/O lug: Wire connected to the PFI capacitor terminals without lug
- W/O Lug: Connection without lug at earth bar
- W/O Lug: Connection without lug at neutral bar
- W/O Lug: Earthing connected with x-former body w/o lug
- Water: Rain water enters into the substation
- Water dropping on the board
- Water dripping on exhaust fan
- Water line (tap) touching (adjacent to) the Panel
- Water line (tap) touching (adjacent to)/near the socket
- Water line (tap) touching (adjacent to)/near the switch-board
- Water line (tap) touching (adjacent to)/near to the light/light shed
- Measurement, Current, voltage measurement for all circuits in the LT,DB,MDB,SDB with connected load
- Insulation resistance, leakage current measurement for all power cables.
- Earth resistance test for all earth pits.
- Thermal scanning for all electrical joints. ( Transformer, Generator, LT, MDB,DB,SDB, power cables, Floor electrical joints general views)
- Earth continuity test for the electrical equipment and related accessories as sample bases.
- Document checking, Previous inspection result, notice for periodic inspection
- Design drawing, As built drawing, layout drawing, approved electrical demand note etc.